: The mechanical or electrical failure of the spindle speed switching contactors themselves.
| User scenario | Fix | |---------------|-----| | After cleaning machine, oil got into fiber optic port | Cleaned with lint-free swab and IPA | | Machine sat for weeks, alarm on restart | Reseated both fiber cables → alarm cleared | | Intermittent alarm when cabinet door moved | Found loose fiber optic connector; replaced cable | | New spindle amp installed → 7115 | Needed to change serial link parameter (Pr 190? or similar) | | Random 7115 on hot days | Cooling fan on electrical cabinet failed; amp overheating | fanuc 7115 alarm
| Step | Action | | :--- | :--- | | | Power off and on the CNC. Sometimes the alarm occurs due to a transient state. | | 2 | Manually jog the axis to the middle of its travel range, away from the decel dog. Then attempt reference return again. | | 3 | Check the deceleration dog (limit switch or proximity sensor). Ensure it is not stuck in the active (depressed) state when the axis is away from it. | | 4 | Monitor the decel dog signal on the PMC diagnostic screen: Typically X address (e.g., X9.0 for Z-axis). The signal should be 1 when the dog is not activated, and 0 when the axis is on the dog. If reversed, invert the signal logic in PMC or check wiring. | | 5 | Check Parameter 3004#5 (RCD) – Set to 1 to disable the direction check (temporary workaround only for testing). If alarm disappears, the root cause is a configuration or hardware direction issue. | | 6 | Check Parameter 1006#5 for the axis. If 0: reference return in + direction. If 1: reference return in – direction. Confirm this matches the physical decel dog placement and machine design. | : The mechanical or electrical failure of the